General Notice
-
Any handling of
WF6 must be authorized by the lab manager and the lab manager must
be present in the lab at the time of the operation.
This includes any activities taking place within the gas cabinet
(which include cylinder installation or cycle purge of the gas
lines) as well as certain activities on the process tool itself such
as opening a gas line which has be exposed to WF6 upstream or
downstream to the tool.
-
For the Venturi
vacuum generator to work properly, the N2 inlet pressure upstream to
the generator must be at least at 120 psi.
If the pressure is below 120 psi, the Venturi will fail and no
vacuum will be generated.
2.1 Gas
cylinder receiving
Delivery of SiH4
and WF6 cylinders will be coordinated with the supplier
(Air Products) and received at the rear entrance of the JM Patterson
Building. Before entering the building the cylinder will be
inspected for signs of a leak (discoloring or residue) and then will
be transported to the LAMP facility and placed in a cabinet until
installation.
2.2 First time
installation of new cylinder
This procedure
is for installation of a new cylinder on to gas system which has not
been previously used with process gases.
2.2.1 Cycle purge and leak check process line
Pump out the
line upstream of the regulator using through the process tool.
a) Pump the
chamber thru the turbo and monitored by the ion gauge.
b) Close VS4
c) Open the process valves (PVs) and set the MFC to full open.
d) Pump on the reactor chamber using the turbo pump.
e) After reaching a base pressure (pump for at least 15 minutes)
at the ion gauge, close the process valve immediately down stream of
the MFC.
f) After approximately 60 sec open this valve and monitor the
effect at the ion gauge.
· A
significant pressure jump MAY signify be a leak in the process
plumbing. If this is observed, repeat the test after pumping on the
chamber for another 15 minutes.
2.2.2 Installing and activation new cylinder
Step 1:
Connect the cylinder to the gas panel
a) Secure
cylinder in place in the gas cabinet
b) Remove cylinder cap
c) Install the pig tail and make sure all the valves are closed
Step 2: Cycle
purge the gas panel
Starting with
all valves closed.
a) Open VS5 to
start N2 flow through the venturi element to generate a vacuum at
VS2.
b) Open VS3 and set the regulator open to near full pressure
delivery. c) Open VS1 fill the panel with purge N2 and then
close VS1.
d) Open VS2 to evacuate the panel, checking for a pressure drop
to near 30" Hg at the regulator low P side.
e) Close VS2.
f) Repeat steps c and d AT LEAST 15 times.
g) Complete this procedure with step d.
h) Leave the system for overnight noting the pressure at the
regulator gauge.
i) If the next day the pressure has not rised, close VS3 and
proceed to the next step.
Step 3: Cycle
purge the process line.
Deliver N2 to
the process line from the purge cylinder.
a) Open VS1 to
apply pressure to the panel.
b) Open VS3 and set pressure at regulator to ~ 10 psi.
c) Open VS4 to pressurize the process line with the purge N2.
d) Close VS4.
e) Put the WF6 MFC in full open and open the upstream PV.
f) Open the By-Pass PV to evacuate process line back to the
cylinder valve VS4.
g) Close the By-Pass PV.
h) Open VS4 to fill the process line, then close VS4
i) Repeat steps f through h at least 10 times.
j) End the process with step g, evacuating the process line.
k) Cycle Purge the panel (see above Step 2) and leave in
evacuated state.
Step 4: Open
the cylinder
Start with all
valves closed. Verify that downstream process valves are closed.
a) Verify that
the electronic switch for the main cylinder valve is OFF.
b) Open the WF6 main cylinder valve at the remote panel.
c) Open VS3 and check pressure at the panel regulator.
d) Open VS4.
2.3
Switching cylinders
2.3.1
Removal of used cylinder
Verify that the
gas cylinder main valve is closed.
Disconnect the
air line to the pneumatically operated main cylinder valve.
Step 1 Cycle
purge the panel.
Starting with
all valves closed.
a) Open VS5 to
start N2 flow through the Venturi element to generate a vacuum at
VS2.
b) Set the regulator open to near full pressure delivery.
c) Open VS2 to evacuate the panel, checking for a pressure drop
to near 30" Hg at the regulator low P side.
d) Close VS2.
e) Open VS1 to fill the panel with purge N2.
f) Close VS1.
g) Repeat steps c and d AT LEAST 10 times.
h) Open VS1 and pressurize the panel with purge gas to provide
outward purge flow when the pigtail connection is disconnected.
Step 2
Disconnect and remove the used cylinder
a) VERIFY that
the pneumatic air line to the main cylinder valve is disconnected or
that the valve is closed (if manual valve).
b) Slowly loosen CGA cylinder fitting and disconnect.
c) Place cap over cylinder valve.
d) Remove cylinder and store for pick-up.
2.3.2
Installation of new cylinder
Step 1:
Connect the cylinder to the gas panel
e) Secure
cylinder in place in the gas cabinet
f) Remove cylinder cap
g) Attach the pigtail fitting to the cylinder.
Step 2: Cycle
purge the gas panel
Start with
VS1 open, all other valves closed.
a) Open VS5 to
start N2 flow through the venturi element to generate a vacuum at
VS2.
b) Open VS3 and set the regulator open to near full pressure
delivery.
c) Close VS1
d) Open VS2 to evacuate the panel, checking for a pressure drop
to near 30" Hg at the regulator low P side.
e) Close VS2.
f) Open VS1
g) Repeat steps c and d AT LEAST 10 times.
h) Complete this procedure with step e (panel evacuated).
i) Leave the system overnight noting the pressure at the
regulator gauge. [A pressure rise is associated with a leak in the
panel or the CGA connection.]
j) If no signs of a leak is detected, proceed to step 3.
Step 3: Open
the cylinder
Start with all
valves closed. Verify that downstream process valves are closed.
a) Verify that
the electronic switch for the main cylinder valve is OFF.
b) Open the WF6 main cylinder valve at the remote panel.
c) Open VS3 and check pressure at the panel regulator.
d) Open VS4. |